SQUARE D BDA260701 Molded Case Circuit Breaker, 70A, 2P, I-Line, 18kAIC @ 480V

Item: CE6HWB
Model: BDA260701
In Stock : 13 Units

Get it by Tuesday, Apr 14

We deliver to your doorstep under DAP terms. Customs clearance is for your account

2
£986.25
5.00% off
£936.94/unit (ex. VAT)
Trade Prices Available
Request Quote

Payment

Delivery

Specifications

Item Circuit Breaker
Ac Voltage Rating 525V AC
Ambient Air Temp. For Operation -13°F to +158°F
Ambient Air Temp. For Storage -58°F to +185°F
Amps 70A
Awg Gauge 14 AWG to 2/0 AWG
Breaking Capacity 25 kA 208Y/120V AC 50/60 Hz UL 489, 25 kA 240V AC 50/60 Hz UL 489, 18 kA 480/277V AC 50/60 Hz UL 489, 18 kA 480V AC 50/60 Hz UL 489, 14 kA 600Y/347V AC 50/60 Hz UL 489, 10 kA 250V DC UL 489
Breaking Capacity Code D
Circuit Breaker Actuator Toggle
Circuit Breaker Application HACR Rated
Circuit Breaker Mounting Style I-Line
Circuit Breaker Type Standard
Color Gray
Component Type Circuit Breaker
Connection Pitch 1.06"
Continuous Amps Rating 80%
Control Type Toggle
Dc Voltage Rating Not Rated
Depth 3.5"
Device Application Distribution
Electrical Connection I-Line Connection, Line, Lugs, Load
Electrical Durability 10000 Cycles
For Use With Electrical Distribution Equipment, Industrial Control Panels
Frame Size 125A, BD
Frame Type BDA
Height 5.39"
Ik Degree Of Protection IK07
Instantaneous Trip Fixed
Ip Degree Of Protection IP40
Line Rated Amps 70A
Local Signalling Presence Of Auxiliary Contacts Flag Green
Max. Air Rating 25 kA At 277/408V AC
Max. Operating Temp. 158°F
Max. Wire Size 2 AWG
Mechanical Durability 20000 Cycles
Min. Operating Temp. -13°F
Min. Wire Size 14 AWG
Mounting Height 3"
Mounting Mode I Line
Network Frequency 50/60 Hz
No. Of 9 Mm Pitches 6
No. Of Poles 2
Number Of Poles 2
Number Of Slots 2
Operating Altitude 0 ft. to 6561.68 ft. Without Derating, 5000m With Derating
Phase Single
Phase Connection AB
Pollution Degree 3 IEC 60947-1
Power Wire Stripping Length 0.8"
Quality Labels ce.png
Quantity Per Set Set of 1
Rated Impulse Withstand Voltage 8 kV
Rated Insulation Voltage 800V
Rated Operational Voltage 525V
Rated Service Breaking Capacity 25 kA @ 220-240V AC @ 50/60 Hz, 14 kA @ 500-525V AC @ 50/60 Hz, 18 kA @ 380-415V AC @ 50/60 Hz, 18 kA @ 440V AC @ 50/60 Hz
Returnability Yes
Suitability For Isolation Yes, IEC 60947-2
Terminal Connection Al Mechanical Lug Off End, I-Line On End
Tightening Torque 31.9 lbf.in. to 38.9 lbf.in. @ 0.004 sq. in. to 0.009 sq. in. @ 14 AWG to 10 AWG, 44.3 lbf.in. to 54.9 lbf.in. @ 0.02 sq. in. to 0.1 sq. in. @ 8 AWG to 2/0 AWG
Trip Type Thermal Magnetic
Trip Unit Technology Thermal-Magnetic
Utilisation Category Category A
Voltage 600V
Voltage Type AC
Width 2.13"
standard CSA C22.2 NO 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB1, NMX J-266, UL 489

Product Details

    • Square D BDA260701 circuit breaker ideal for preventing damage to electrical equipment due to current overloads or short circuits
    • Features thermal-magnetic trip unit offering instantaneous and long-time current limiting functions
    • Equipped with lug terminals to accommodate wires (copper / aluminium) of sizes ranging between 14 & 2/0 AWG
    • Unique I-Line style plug-in with load side lugs provides easy installation and repairs
    • Meets UL, CSA and IEC standards

Shipping Information

height 13.69
length 8.89
width 5.41
country of origin MX
weight 0.630000

Contact Us

Contact your account manager right away to get personal advice.
We're available Monday through Friday, from 07:30 until 17:00.